Energy efficiency enhancements to a low energy high performance building

Thumbnail Image
Date
2008-01-01
Authors
Logan, Joel
Major Professor
Advisor
Michael B. Pate
Ron M. Nelson
J. Adin Mann
Committee Member
Journal Title
Journal ISSN
Volume Title
Publisher
Altmetrics
Authors
Research Projects
Organizational Units
Organizational Unit
Mechanical Engineering
The Department of Mechanical Engineering at Iowa State University is where innovation thrives and the impossible is made possible. This is where your passion for problem-solving and hands-on learning can make a real difference in our world. Whether you’re helping improve the environment, creating safer automobiles, or advancing medical technologies, and athletic performance, the Department of Mechanical Engineering gives you the tools and talent to blaze your own trail to an amazing career.
Journal Issue
Is Version Of
Versions
Series
Department
Mechanical Engineering
Abstract

This report discusses energy efficiency enhancements made to a low energy, high performance office building. The building studied is the Iowa Association of Municipal Utilities headquarters located in Ankeny, Iowa, just north of Des Moines. Monitoring the energy use of the building for over six years has revealed that it has an average annual site energy use of 29,300 Btu/ft2. This is 68% less energy than that used by the average U.S. office building and 74% less energy than the average office building in climate zone 2, the location of Ankeny.;Three areas of energy use were chosen for improvement: the ground source heat pump system's circulating pump, the energy recovery ventilator's defrost heater, and general office equipment (computers, refrigerators, coffee pot, etc.) during periods when the building is unoccupied. Before the improvements, the three items contributed to 38% of the building's annual energy use. The table below summarizes the energy use of each item before improvements were made, and the savings resulting from the improvements. The improvements have the potential of saving up to 27% of the building's annual energy use. The circulating pump's energy savings were achieved by switching it from a constant speed pump to a variable speed pump by equipping it with a variable frequency drive and installing shutoff valves on the heat pumps. Energy savings for the defrost heater were realized by decreasing its set point from an unreasonable 46°F to a recommended 5°F. The savings for the general equipment can be achieved if employees turn off all unnecessary equipment when the building is unoccupied.

Comments
Description
Keywords
Citation
Source
Copyright
Tue Jan 01 00:00:00 UTC 2008